Tinned or bare. stranded or solid copper conductor. 32-4/0AWG. Crosslinked XLPE insulation Jacket PVC
lettering:E511615 兄 AWM 3386 105℃ 600V ---- C兄 AWM I A 105℃ 600V FT2 KINGPOWER
Rated temperature :105℃
Rated voltage :600V
Reference standard :UL 758,UL1581
Passes Horizontal flame
| Conductor | XLPE Insulation | PVC Jacket | Max. DC Resistance at 20°C (ohm/km) | ||||
|---|---|---|---|---|---|---|---|
| AWG | NO./mm | Diameter (mm) | Thickness (mm) | Diameter (mm) | Thickness (mm) | Diameter (mm) | |
| 32 | 7/0.08 | 0.244 | 0.762 | 1.8 | 0.762 | 3.35 | 601.0 |
| 30 | 7/0.10 | 0.306 | 0.762 | 1.85 | 0.762 | 3.4 | 381.0 |
| 28 | 7/0.127 | 0.388 | 0.762 | 1.95 | 0.762 | 3.5 | 239.0 |
| 26 | 7/0.16 | 0.489 | 0.762 | 2.05 | 0.762 | 3.6 | 150.0 |
| 24 | 11/0.16 | 0.61 | 0.762 | 2.15 | 0.762 | 3.7 | 94.2 |
| 22 | 17/0.16 | 0.76 | 0.762 | 2.3 | 0.762 | 3.85 | 59.4 |
| 20 | 26/0.16 | 0.94 | 0.762 | 2.5 | 0.762 | 4.05 | 36.7 |
| 18 | 41/0.16 | 1.18 | 0.762 | 2.75 | 0.762 | 4.3 | 23.2 |
| 16 | 65/0.16 | 1.49 | 0.762 | 3.05 | 0.762 | 4.6 | 14.6 |
| 14 | 41/0.254 | 1.87 | 0.762 | 3.4 | 0.762 | 3.95 | 8.96 |
| 12 | 65/0.254 | 2.36 | 0.762 | 3.9 | 0.762 | 5.45 | 5.64 |
| 10 | 105/0.254 | 3 | 0.762 | 4.55 | 0.762 | 6.1 | 3.55 |
| 9 | 126/0.254 | 3.85 | 0.762 | 5.4 | 0.762 | 6.95 | 2.81 |
| 8 | 165/0.254 | 4.4 | 1.143 | 6.7 | 0.762 | 8.25 | 2.23 |